dc.identifier.citation |
Cite this article as: L. G. Obregon, J. C. Pertuz, R. A. Dominguez, “Performance analysis of a laboratory scale cooling tower for diferent packing materials, water inlet temperature and mass low ratio wat-earir”, Prospectiva, Vol 15, N° 1, 42-52, 2017. |
es |
dc.identifier.issn |
22161368 Versión Web. |
|
dc.identifier.uri |
http://hdl.handle.net/11619/3043 |
|
dc.identifier.uri |
http://ojs.uac.edu.co/index.php/prospectiva/article/view/820/pdf_54 |
|
dc.description.abstract |
En el presente trabajo se realizó el diseño, montaje y puesta en marcha de una torre de enfriamiento a
escala de laboratorio de 0.15 m de lado y 1.54 m de alto, adecuada con empaques tipo salpicadura hechos
de madera, acrílico, hierro y aluminio, y de tipo película hecho de acrílico. Se evaluó el desempeño de
la torre a diferentes relaciones de flujo másico L´/G´ en el rango de 0.2 a1.0, temperaturas de entrada
de líquido en el rango 48-40°C y diferentes materiales y geometrías de empaque. Se desarrolló una
correlación no lineal del coeficiente volumétrico global de transferencia de masa Kya como función de
los diferentes factores estudiados mediante análisis estadístico. Se notó que el desempeño de la torre de
enfriamiento mejora en altos valores de Kya y de eficiencia global cuando se realizaron incrementos de la
relación L´/G´ operando con empaques que contienen valores bajos de conductividad térmica tal como la
madera y el acrílico y usando altos valores de la temperatura del agua de entrada. Un aumento en el área
superficial del empaque de un 350% resulta en un incremento en eficiencia hasta de un 30% mostrando
la importancia de realizar un análisis de costos de ingeniería. |
es |
dc.description.abstract |
ABSTRACT:
In this work it was performed the design, assembling and start up of a laboratory scale cooling tower
with 0.15 m side and 1.54 m high, equipped with splash type packaging made of wood, acrylic plastic,
iron and aluminum, as well as a film type packing made of acrylic material. The performance of the
tower was evaluated at diferent mass flow ratios L´/G´ in the range of 0.2-1.0, liquid inlet temperature
between 48-40°C and diferent material and geometry of the tower packing. It was obtained a non-linela
correlation of the total volumetric mass transfer coefficient Kya as a function of the diferent factors
studied using a statistical analysis. It was observed that the performance of the cooling tower improves
to high values of Kya and eficiency in the tower when increasing the relation L´/G´ working with tower
packing with flow thermal conductivity such as wood and acrylic material, and using high values of inlet
water temperature. An increase in the surface area of the tower packing to 350% results in an increase
in the eficiency to approximately 30% showing the importance of making an engineering cost analysis. |
|
dc.language.iso |
es |
es |
dc.publisher |
Universidad Autónoma del Caribe. |
es |
dc.relation.ispartofseries |
Vol 15, N° 1, 42-52, 2017; |
|
dc.subject |
Torre de enfriamiento |
es |
dc.subject |
Desempeño |
es |
dc.subject |
Eficiencia |
es |
dc.subject |
Correlación no lineal |
es |
dc.subject |
Coeiciente volumétrico de transferncia de masa |
es |
dc.subject |
Empaque de torre |
es |
dc.title |
Análisis del desempeño de una torre de enfriamiento a escala de laboratorio para diversos materiales de empaque, temperatura de entrada de agua y relación másica de flujo agua-aire / |
es |
dc.title.alternative |
Performance analysis of a laboratory scale cooling tower for different packing materials, water inlet temperature and mass flow ratio water-air / |
es |
dc.type |
Article |
es |