dc.description.abstract Los sistemas de refrigeración a lo largo de su existencia le han brindado infinidad de soluciones al ser humano, desde la conservación de alimentos hasta la climatización de un recinto para llegar a un estado de confort térmico, sin embargo los refrigerantes que se han utilizado hasta hace unos pocos años han venido degradando el entorno de una manera u otra. El problema que deseamos resolver específicamente es como en Colombia se prohibirá el R22 para dentro de 5 años, hacer un estudio mediante pruebas experimentales para tomar una conclusión si el R134a puede sustituirlo, y que consecuencias tendría en la eficiencia de las maquinas que estamos utilizando, es decir bajo qué condiciones de uso el refrigerante R134a sería una buena alternativa de reemplazo para el R22. La metodología para desarrollar este experimento es tomar los niveles máximos de la presión de alta, en base al correcto funcionamiento del equipo, indicado por los pre experimentos, de flujos de agua en los evaporadores y condensadores respectivos. En este caso se debe experimentar con el equipo hasta tener una diferencia de temperatura en el condensador y el evaporador de agua, que pueda apreciarse sin problemas y que se estabilice en sus valores, esto sucede desde la apertura a nivel medio de las válvulas de flujo de agua para evaporador y condensador. De esta manera el equipo funciona a régimen máximo con el refrigerante (máxima presión, máximo caudal), resultando los valores que corresponden a las diversas variables de respuesta medidas por el software. Al obtener los resultados se ha dado cuenta que para el caso del análisis comparativo, puede decirse que para uso de refrigeración, la sustitución del R22 por el R134a puede hacerse, esperando un manejo menor de la carga térmica manejada, por lo que debe evaluarse cada aplicación. es
dc.description.abstract Abstract: Cooling systems throughout its existence have given you a host of solutions to the human being from food preservation to the climate of a room to reach a state of thermal comfort, however refrigerants have been used until recently a few years they have to degrade the environment in one way or another. The problem we want to solve is as in Colombia specifically R22 to within 5 years will be banned, a study by experimental evidence to make a conclusion whether the R134a can replace it, and what consequences would have on the efficiency of the machines we are using, ie under what conditions of use R134a be a good alternative replacement for the R22. The methodology for developing this experiment is to take the maximum pressure levels high, based on the correct operation of the equipment indicated by the pre experiments, water flows in the evaporators and respective capacitors. In this case you should experiment with the team until a temperature difference in the condenser and evaporator water that can be seen without problems and to stabilize at their values, this happens from the opening to mid-level flow valves water for evaporator and condenser. In this way the equipment operates at maximum speed with coolant (maximum pressure, maximum flow) resulting values corresponding to the different response variables measured by the software. To obtain the results has noticed that in the case of the comparative analysis, use can be said that for cooling, the substitution of R22 with R134a may be waiting a lower thermal management of cargo handled, so it must be evaluated each application. The cooling effect decreased by 6% for the conditions imposed in testing, but also for the use of R134a is under high pressure values, which helps lower power consumption, assuming that the cooling reduction tolerated. en
dc.language.iso es es
dc.publisher Universidad Autónoma del Caribe es
dc.subject Refrigeración -- Estudio de Casos es
dc.title Caracterización del desempeño de los refrigerantes R134a y R22 estudiados en el laboratorio de plantas térmicas de la Universidad Autónoma Del Caribe. es
dc.type Working Paper es
dcterms.contributor Saltarín Jiménez, Antonio Manuel (asesor) es